IFM PQC612 压力传感器

IFM

IFM PQC612 压力传感器

用于气动装置的压力传感器

IFM PQC612 压力传感器 — datasheet、规格参数、订货号查询与原装正品采购

获取报价 / 询盘

立即询价 WhatsApp 询盘 邮件询价

产品亮点

产品概述

产品标识电子压力传感器
应用用于工业应用
系统接口螺纹连接 1/8" NPT 内螺纹 (2x)
工作电压DC18...30 V
电压类型DC
电气设计PNP/NPN
输出数量2
输出功能常开/常闭; (可设定参数); 模拟
输出信号开关信号; 模拟信号; IO-Link; (可配置)
模拟电流输出4...20, 可逆; (可调整量程) mA
模拟电压输出0...10 / 1...5, 可逆; (可调整量程) V
测量范围-1...10 bar-14.5...145 psi
接口M8 接插件
原材料PBT; PC; TPE; 丁晴橡胶; FKM; 黄铜; 硅(镀层)
材料(接液部件)PBT; FKM; 黄铜; 硅(镀层)
显示显示 1": 128 x 96 像素; 开关状态: 1 x LED 黄色
环境温度0...60 °C
介质温度0...60 °C
通信接口IO-Link
产品易福门或同价值的
型号PQC612

技术规格

Product characteristics
Number of inputs and outputsNumber of digital outputs: 1; Number of analogue outputs: 1
Measuring range
-1...10 bar-14.5...145 psi
Process connectionthreaded connection 1/8" NPT internal thread (2x)
Application
Special featureGold-plated contacts
Applicationfor industrial applications
Mediacompressed air; nitrogen (N2)
Conditionally suitable forother media on request
Medium temperature
0...60 °C32...140 °F
Min. burst pressure
20 bar290 psi
Pressure rating
15 bar220 psi
Vacuum resistance
-1000 mbar-14.5 psi
Type of pressurerelative pressure; vacuum
Electrical data
Operating voltage[V]18...30 DC
Current consumption[mA]< 30
Min. insulation resistance[MΩ]100; (500 V DC)
Protection classIII
Reverse polarity protectionyes
Power-on delay time[s]0.3
Integrated watchdogyes
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 1; Number of analogue outputs: 1
Outputs
Total number of outputs2
Output signalswitching signal; analogue signal; IO-Link; (configurable)
Electrical designPNP/NPN; (configurable)
Number of digital outputs1
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output DC[V]2.5
Permanent current rating of switching output DC[mA]100
Switching frequency DC[Hz]< 170
Number of analogue outputs1
Analogue current output[mA]4...20, invertible; (scalable)
Max. load[Ω]500
Analogue voltage output[V]0...10 / 1...5, invertible; (scalable)
Min. load resistance[Ω]2000
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Measuring/setting range
Measuring range
-1...10 bar-14.5...145 psi
Set point SP
-1...10 bar-14.5...145 psi
Analogue start point
-1...8 bar-14.5...116 psi
Analogue end point
1...10 bar14.5...145 psi
In steps of
0.01 bar0.1 psi
Accuracy / deviations
Switch point accuracy[% of the span]< ± 0,5; (turn down 1:1)
Repeatability[% of the span]< ± 0,1; (with temperature fluctuations < 10 K: turn down 1:1)
Characteristics deviation[% of the span]< ± 0,5; (turn down 1:1; including linearity, hysteresis and repeatability)
Linearity deviation[% of the span]< ± 0.5 % (limit value setting according to DIN EN IEC 62828-1) turn down 1:1
Hysteresis deviation[% of the span]< ± 0,25; (turn down 1:1)
Long-term stability[% of the span]< ± 0,1; (turn down 1:1; per year)
Temperature coefficient zero point[% of the span / 10 K]0,2; (Turn down 1:1)
Temperature coefficient span[% of the span / 10 K]0,2; (Turn down 1:1)
Response times
Response time[ms]6
Damping process value dAP[s]0...4
Damping for the analogue output dAA[s]0...99.99
Software / programming
Parameter setting optionsdisplay can be rotated and switched off; analogue output selectable and scalable; Teach function; simulation function; diagnostic function
Interfaces
Communication interfaceIO-Link
IO-Link revision1.1.3
SDCI standardIEC 61131-9: 2019-06
SIO modeyes
Required master port typeA
Process data analogue1
Process data binary2
IO-Link resolution pressure[bar]0.001
IO-Link process data (cyclical)
functionbit length
pressure16
device status4
SSC1.11
SSC1.21
IO-Link functions (acyclical)application specific tag; internal temperature; Medium temperature
Supported DeviceIDs
Type of operationDeviceID
default1717
Operating conditions
Ambient temperature
0...60 °C32...140 °F
Storage temperature
-25...85 °C-13...185 °F
ProtectionIP 65
Tests / approvals
EMC
DIN EN 61326-1
Shock resistance
DIN EN 60068-2-2750 g (11 ms)
Vibration resistance
DIN EN 60068-2-620 g (10...2000 Hz)
UL approval
UL approval no.J067
File number ULE174189
Pressure Equipment DirectiveSound engineering practice; can be used for stable gases fluid group 2
Mechanical data
Weight[g]53.1
Housingrectangular
Dimensions[mm]37.7 x 30 x 38.6
MaterialsPBT; PC; TPE; NBR; FKM; brass; silicon (coated)
Materials (wetted parts)PBT; FKM; brass; silicon (coated)
Min. pressure cycles50 million
Process connectionthreaded connection 1/8" NPT internal thread (2x)
Displays / operating elements
Display
Display 1"128 x 96 pixels
switching status1 x LED, yellow
Display unitbar; MPa; psi; mmHg; inHg; kgf/cm²
Accessories
Items suppliedhead cap screw: 2 x (M3 x 8 mm)
Remarks
Pack quantity1 pcs.
Electrical connection
Connector1 x M8; coding: A; Contacts: 4, gold-plated

下载资料