IFM PN7071 压力传感器

IFM

IFM PN7071 压力传感器

带显示屏的压力传感器

IFM PN7071 压力传感器 — datasheet、规格参数、订货号查询与原装正品采购

获取报价 / 询盘

立即询价 WhatsApp 询盘 邮件询价

产品亮点

产品概述

产品标识电子压力传感器
应用用于工业应用
系统接口螺纹连接 G 1/4 内螺纹
工作电压DC18...30 V
电压类型DC
电气设计PNP/NPN
输出数量2
输出功能常开/常闭; (可设定参数)
输出信号开关信号; IO-Link; (可配置)
测量范围0...250 bar0...3620 psi0...25 MPa
接口M12 接插件
原材料不锈钢 (630/1.4542 /17-4 PH); 不锈钢(1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC
材料(接液部件)不锈钢 (630/1.4542 /17-4 PH)
显示显示单位: 3 x LED 绿色 (bar, psi, MPa); 开关状态: 2 x LED 黄色; 测量值: 字母数字显示 红色/绿色 4位数字
环境温度-25...80 °C
介质温度-25...80 °C
通信接口IO-Link
产品易福门或同价值的
型号PN7071

技术规格

Product characteristics
Number of inputs and outputsNumber of digital outputs: 2
Measuring range0...250 bar 0...3620 psi 0...25 MPa
Process connectionthreaded connection G 1/4 internal thread
Application
Special featureGold-plated contacts
Measuring elementmetallic thin film cell
Applicationfor industrial applications
Medialiquids and gases
Medium temperature[°C]-25...80
Min. burst pressure1100 bar 15950 psi 110 MPa
Pressure rating500 bar 7250 psi 50 MPa
Vacuum resistance
-1000 mbar-0.1 MPa
Type of pressurerelative pressure
Electrical data
Operating voltage[V]18...30 DC; (to SELV/PELV)
Current consumption[mA]< 35
Min. insulation resistance[MΩ]100; (500 V DC)
Protection classIII
Reverse polarity protectionyes
Power-on delay time[s]< 0.3
Integrated watchdogyes
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 2
Outputs
Total number of outputs2
Output signalswitching signal; IO-Link; (configurable)
Electrical designPNP/NPN
Number of digital outputs2
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output DC[V]2.5
Permanent current rating of switching output DC[mA]150; (200 (...60 °C) 250 (...40 °C))
Switching frequency DC[Hz]< 170
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Measuring/setting range
Measuring range0...250 bar 0...3620 psi 0...25 MPa
Factory setting / CMPT = 2
Set point SP2...250 bar 40...3620 psi 0.2...25 MPa
Reset point rP1...249 bar 20...3600 psi 0.1...24.9 MPa
Min. difference between SP and rP2 bar 20 psi 0.2 MPa
In steps of1 bar 20 psi 0.1 MPa
Status_B High Resolution / CMPT = 3
Set point SP2...250 bar 30...3626 psi 0.2...25 MPa
Reset point rP1...249 bar 12...3608 psi 0.1...24.9 MPa
Min. difference between SP and rP2 bar 19 psi 0.2 MPa
In steps of1 bar 1 psi 0.1 MPa
Accuracy / deviations
Switch point accuracy[% of the span]< ± 0,5
Repeatability[% of the span]< ± 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation[% of the span]< ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation[% of the span]< ± 0,25
Long-term stability[% of the span]< ± 0,05; (per 6 months)
Temperature coefficient zero point[% of the span / 10 K]0,2; (-25...80 °C)
Temperature coefficient span[% of the span / 10 K]0,2; (-25...80 °C)
Response times
Response time[ms]< 3
Delay time programmable dS, dr[s]0...50
Software / programming
Parameter setting optionshysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit
Interfaces
Communication interfaceIO-Link
Transmission typeCOM2 (38,4 kBaud)
IO-Link revision1.1
SDCI standardIEC 61131-9
SIO modeyes
Required master port typeA; (when pin 2 not connected: B)
Process data analogue1
Process data binary2
Supported DeviceIDs
Type of operationDeviceID
Factory setting / CMPT = 2400
Status_B High Resolution / CMPT = 3598
NoteFor further information please see the IODD PDF file under "Downloads"
Factory setting / CMPT = 2
Profiles
Smart Sensor - SSP 0Generic Profiled Sensor
FunctionDevice identification
FunctionProcess data variable
FunctionDevice diagnosis
Min. process cycle time[ms]2.3
IO-Link resolution pressure
1 bar0.1 MPa
IO-Link process data (cyclical)
functionbit length
pressure14
binary switching information2
IO-Link functions (acyclical)application specific tag
Status_B High Resolution / CMPT = 3
Profiles
Smart Sensor - SSP 3.1Measuring Sensor
Common - I&DIdentification and Diagnosis
Min. process cycle time[ms]3
IO-Link resolution pressure
0.1 bar0.01 MPa
IO-Link process data (cyclical)
functionbit length
pressure16
device status4
binary switching information2
IO-Link functions (acyclical)application specific tag
Operating conditions
Ambient temperature[°C]-25...80
Storage temperature[°C]-40...100
ProtectionIP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-2750 g (11 ms)
Vibration resistance
DIN EN 60068-2-620 g (10...2000 Hz)
MTTF[years]214
UL approval
UL approval no.J003
Pressure Equipment DirectiveSound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight[g]239.2
Housingcylindrical
Dimensions[mm]Ø 34 / L = 90.7
Materialsstainless steel (630/1.4542/17-4 PH); stainless steel (316L/1.4404); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts)stainless steel (630/1.4542/17-4 PH)
Min. pressure cycles100 million
Tightening torque[Nm]25...35; (recommended tightening torque; depends on the lubrication, the seal and the pressure load)
Process connectionthreaded connection G 1/4 internal thread
Restrictor element integratedno (can be retrofitted)
Displays / operating elements
Display
Display unit3 x LED, green (bar, psi, MPa)
switching status2 x LED, yellow
measured valuesalphanumeric display, red/green 4-digit
Remarks
Pack quantity1 pcs.
Electrical connection
Connector1 x M12; coding: A; Contacts: 4, gold-plated

下载资料