IFM PN4226 Pressure Sensors

IFM

IFM PN4226 Pressure Sensors

Pressure sensor with display

IFM PN4226 Pressure Sensors — datasheet, specifications, part number lookup & authentic sourcing

Get a Quote / Inquire

Request a Quote Chat via WhatsApp Email Us

Product Highlights

Overview

Product designationElectronic pressure monitor
Applicationfor industrial applications
Process connectionthreaded connection 1/4" NPT internal thread
Operating voltage AC90...250 V
Voltage typeAC
Electrical designTriac
Total number of outputs1
Output functionnormally open / normally closed; (parameterisable)
Output signalswitching signal
Measuring range0...2.5 bar0...2500 mbar0...36.3 psi0...250 kPa
Connection1/2" Connector
Materialsstainless steel (304/1.4301); PC; PBT; PA; FKM
Materials (wetted parts)stainless steel (303/1.4305); ceramics; FKM
Displayswitching status: LED red; function display: 7-segment LED display; measured values: 7-segment LED display
Ambient temperature-25...80 °C
Medium temperature-25...80 °C
Brandifm electronic gmbh or equivalent
TypePN4226

Specifications

Product characteristics
Number of inputs and outputsNumber of digital outputs: 1
Measuring range0...2.5 bar 0...2500 mbar 0...36.3 psi 0...250 kPa
Process connectionthreaded connection 1/4" NPT internal thread
Application
Applicationfor industrial applications
Medialiquids and gases
Medium temperature[°C]-25...80
Min. burst pressure50 bar 725 psi 5000 kPa
Pressure rating20 bar 290 psi 2000 kPa
Type of pressurerelative pressure
Electrical data
Operating voltage tolerance[%]5...10
Operating voltage[V]90...250 AC
Nominal voltage AC[V]< 250
Current consumption[mA]< 10
Min. insulation resistance[MΩ]100; (500 V DC)
Protection classII
Reverse polarity protectionno
Power-on delay time[s]0.2
Integrated watchdogyes
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 1
Outputs
Total number of outputs1
Output signalswitching signal
Electrical designTriac
Number of digital outputs1
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output AC[V]2
Permanent current rating of switching output AC[mA]250; ((...70 °C) 1000 (...60 °C) 1500 (...45 °C) 2500 (...20 °C))
Switching frequency AC[Hz]< 160
Short-circuit proofno
Overload protectionno
Measuring/setting range
Measuring range0...2.5 bar 0...2500 mbar 0...36.3 psi 0...250 kPa
Set point SP0.02...2.5 bar 0.4...36.3 psi 2...250 kPa
Reset point rP0.01...2.49 bar 0.2...36.2 psi 1...249 kPa
In steps of0.01 bar 0.1 psi 1 kPa
Accuracy / deviations
Switch point accuracy[% of the span]< ± 1,0
Repeatability[% of the span]< ± 0,1; (with temperature fluctuations < 10 K)
Linearity deviation[% of the span]< ± 0,5
Hysteresis deviation[% of the span]< ± 0,1
Long-term stability[% of the span]< ± 0,1; (per year)
Temperature coefficient zero point[% of the span / 10 K]< ± 0,2; (-25...80 °C)
Temperature coefficient span[% of the span / 10 K]< ± 0,3; (-25...80 °C)
Response times
Delay time programmable dS, dr[s]0, 0,2,...10, 11,...50
Damping process value dAP[s]0...4
Software / programming
Adjustment of the switch pointprogramming button
Parameter setting optionshysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit
Operating conditions
Ambient temperature[°C]-25...80
Storage temperature[°C]-40...100
ProtectionIP 65
Tests / approvals
EMC
EN 61000-4-2 ESD4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated10 V/m
EN 61000-4-4 Burst2 kV
EN 61000-4-6 HF conducted10 V
Shock resistance
DIN IEC 68-2-2750 g (11 ms)
Vibration resistance
DIN IEC 68-2-620 g (10...2000 Hz)
MTTF[years]224.58
Pressure Equipment DirectiveSound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight[g]382.85
Housingcylindrical
Dimensions[mm]Ø 34 / L = 120
Materialsstainless steel (304/1.4301); PC; PBT; PA; FKM
Materials (wetted parts)stainless steel (303/1.4305); ceramics; FKM
Min. pressure cycles100 million
Process connectionthreaded connection 1/4" NPT internal thread
Restrictor element integratedno (can be retrofitted)
Displays / operating elements
Display
switching statusLED, red
function display7-segment LED display
measured values7-segment LED display
Electrical connection
Required protectionminiature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting
Remarks
Remarks
n.c. = not used
Pack quantity1 pcs.
Electrical connection
Connector1 x 1/2"; coding: C; Contacts: 5

Downloads